Supply of FIRE SUPPRESSION SYSTEM
As per RDSO/ SPN/218/2016 Version 1.0- d2.
Design, Supply and Installation of FIRE SUPPRESSION SYSTEM having non-toxic, environment friendly, non-corrosive, clean gaseous agent at the atmospheric pressure, safe for
Electronic /Electrical/ Telecommunication Equipments/Computers, Human Friendly, non-residual, Non-inflammable, type agent Heptafluopropane(C3F7H) (HFC227ea) FM 200 GAS. This system must include hydraulic flow calculations for the suppression areas and vetting of the Software Results from the OEM Factory Engineer. This shall be a Total Flooding system for Relay Room and Equipment Room with Automatic sensing and Activation along with the microprocessor based Advance Multifunction Programmable control panel as detailed in the annexure. The system includes following sub-systems:- 1Nos